| Able to control 1 T4 26 or 32 watt bulb |
| Can be wired as switching ballasts. Do not tie any wires into the E1, E2 terminals and only connect the dim hot terminal in with the switched hot terminal |
| Dims down to 5% |
| Can be controlled through either a Lutron 3-wire fluorescent control or through the EcoSystem data link |
| Require rapid start sockets; will not fire up if instant start sockets are being used |
|
Troubleshooting |
| For additional troubleshooting steps, consult Fluorescent Ballast Troubleshooting PDF below |
| Problem: Lamps flickering on/off continuously |
| Ensure the ballast is being controlled with a Lutron 3-wire fluorscent control or through the EcoSystem data link |
| If using a 3-wire dimmer, ensure the dim hot and switch hot terminals are not reversed |
| If using EcoSystem control, ensure the dim hot terminal is not connected |
| Problem: Lamps flickering on every 7-8 seconds |
| Ensure lamp sockets are wired in parallel and not in a series |
| Ensure lamp wattage matches wattage specified on the ballast |
| Ensure 1 lamp is tied to the ballast |
| Problem: Lamps burning out prematurely |
| Same troubleshooting steps as lamps flickering on every 7-8 seconds (above)
|