| Able to control 3 T8 or U-bend 32 watt bulbs |
| Not compliant with CEC Title 20 |
| Can be wired as switching ballasts. Do not tie any wires into the E1, E2 terminals and only connect the hot and neutral terminals |
| Dims down to 1% |
| Can be controlled through the EcoSystem data link |
| Require rapid start sockets; will not fire up if instant start sockets are being used |
|
| Troubleshooting |
| For additional troubleshooting steps, consult Fluorescent Ballast Troubleshooting PDF below |
| Problem: Lamps flickering on/off continuously |
| Ensure ballast is being controlled through the EcoSystem data link and not through a line voltage dimmer |
| Problem: Lamps flickering on every 7-8 seconds |
| Ensure lamp sockets are wired in parallel and not in a series |
| Ensure lamp wattage matches what is specified on the ballast |
| Ensure number of lamps tied to the ballast matches what is specified on the ballast |
| Problem: Lamps burning out prematurely |
| Same troubleshooting steps as lamps flickering on every 7-8 seconds (above)
|