| Maximum of 5 amps |
| Ground connection is required |
| Sensor can be bypassed to keep the lights on by extending the time out period up to 30 minutes. Cannot override sensor so lights stay on indefinitely |
| Does not detect motion through glass |
|
Troubleshooting |
| Problem: Cannot switch power on or off with a newly installed sensor switch |
| Sensor requires a true earth ground connection in order to operate properly. First ensure that the device's green and bare wires are connected to the ground in your wallbox. If a ground is not available, this device will not function properly. If you do have a ground but are still experiencing this issue, it's possible that the ground wire does not directly return to the breaker panel. In that situation, a true earth ground connection would need to be introduced, or this device may not function properly. If you believe this is the issue, please call Lutron's support line at 844-LUTRON-1 |
| Problem: Lights do not turn on when space is occupied |
| If being used in a 3 or 4-way application, wiring may be incorrect. If using with a 3-way mechanical switch, check wiring changes were made at the mechanical switch per step 3 of the Installation Instructions |
| Sensor is vacancy only model |
| Sensor is set to one of the Ambient Light Detection (ALD) settings and the room is too bright for the current light level setting |
| Sensor does not have full view of the room. Move objects that may be blocking line-of-sight |
| Problem: Lights turn off while space is occupied |
| Sensor's timeout may be too short |
| Sensor's sensitivity may be set for low |
| Sensor may not have full view of the room |
| Problem: Lights will not turn off once space is unoccupied |
| Sensor's timeout may be set for too long |
| An external noise such as an HVAC vent may be interfering with the sensor. Try changing the sensitivity to low |
| Problem: 3-way switch does not turn the lights on |
| 3-way switch may have a locator light, which can affect the sensor's performance. Lutron recommends replacing the 3-way switch with one that does not have a locator light |
| Check wiring in Installation Instructions |
| Problem: Lights turn on in vacancy mode |
| In vacancy mode a 15 second grace period follows the timeout where the sensor will turn back on if it senses motion
|